中性点经消弧线圈接地系统断线故障的异常电压分析
(上海电力学院电力工程系)
Analysis of System of Neutral Grounding Abnormal Voltage through Petersen Coil in Condition of Tripping Fault
(Department of Electric Power Engineering)
摘要
图/表
参考文献
本刊相似文献
All Journals 相似文献
All Journals 引证文献
本文已被:浏览 1145次   下载 480
投稿时间:1995-09-18    
中文摘要: 本文从理论上分析了中性点经消弧线圈接地系统单相断线、两相断线时的过电压,并对实例进行了数值仿真计算,最后提出了降低此过电压的几点措施。
Abstract:In this paper, the overvoltage of the system of neutral grounding through petersen coil in the condition of single-phase tripping and double-phase tripping is analysed theoretically,and an example system is digit simulated. Finally, some measures about reducing this overvoltage are put forward.