DOI:
Journal of ShangHai University of Electric Power :2013,29(4):311-314
View/Add Comment     Archive    Advanced search     HTML
←Previous   |   Next
西双版纳电网短路电流衰减的影响因素
(1.上海电力学院电气工程学院, 上海 200090;2.西双版纳供电局电力调度控制中心, 云南西双版纳 666100)
Influencing Factors on Xishuangbana Grid Short Circuit Decay
(1.School of Electric Power Engineering, Shanghai University of Electric Power, Shanghai 200090, China;2.Power Dispatching Control Center, Xishuangbanna Electic Power Bureau, Xishuangbanna 666100, China)
Abstract
Image-text
References
Similar literature
本文已被:浏览 1139次   下载 604
Received:March 21, 2013    
中文摘要: 在考虑发电机饱和特性、励磁系统及负荷特性等影响因素后,对西双版纳电网的短路电流进行衰减仿真计算。结果表明:发电机饱和特性以及励磁系统对短路电流衰减的影响不大,但负荷尤其是动态负荷对短路电流衰减有较大的影响。这一结果可作为研究与评估西双版纳电网实际短路电流衰减的参考。
中文关键词: 短路电流  衰减  励磁系统  发电机饱和  负荷
Abstract:After taking into consideration the reseach generator saturation, excitation system and the load of short circuit current decay effect, the simulation calculation of the short-circuit of Xishuangbanna grid is conducted. Results show that the generator saturation and excitation system has little effect on the short-circuit current decay, and the load has a greater impact on the shortcircuit current decay, especially dynamic load, which could be used as reference on study and assessment of the actual Xishuangbanna grid short-circuit decay.
文章编号:20130402     中图分类号:    文献标志码:
基金项目:
Reference text: