相控式消弧线圈退出后电压振荡现象分析
(1.上海电力学院;2.上海蓝瑞电气有限公司)
Analysis of Voltage Oscillation after the Phase-controlled Arc Suppression Coil Exiting
(1.Shanghai University of Electric Power, Shanghai 200090, China;2.Shanghai Lanrui Electric Co., Ltd., Shanghai 201613, China)
摘要
图/表
参考文献
本刊相似文献
All Journals 相似文献
All Journals 引证文献
本文已被:浏览 973次   下载 508
投稿时间:2018-04-18    
中文摘要: 单相接地故障消除之后,相控式消弧线圈应退出运行,不再输出补偿电流,中性点电压恢复至正常状态。但在某变电站的录波记录中发现,系统中性点电压呈现出低频振荡的现象。为此,采用电工学的基本原理,分析了产生低频振荡的原因,并通过PSCAD/EMTDC仿真证实了该理论分析的结果。最后,提出了抑制低频振荡的措施。
Abstract:After a single-phase-to-ground fault is eliminated,the phase-controlled arc suppression coil should exit without any compensation currents.Then,the neutral voltage will return to normal state.However,the phenomenon of low-frequency oscillation of the neutral voltage is found in the recording of a substation.For this reason,the basic circuit principles are adopted,the causes of low frequency oscillation are analyzed,and the suppression methods are put forward.Finally,the theoretical analysis is verified through PSCAD/EMTDC simulation.
文章编号:20194008     中图分类号:TM773    文献标志码:
基金项目:上海高校青年教师培养资助计划(ZZsdl15092);上海电力学院人才引进基金(K2014-044)。
引用文本:
徐波,彭耀辉,蔡翔.相控式消弧线圈退出后电压振荡现象分析[J].上海电力大学学报,2019,35(4):345-348,366.